The Stanley Wi-Q Communication Service is started but the workstation name is still not listed in the portals tab in the Configuration program.

Answer 

The data source in the connection strings may be incorrect in the config files. This can happen if the SQL database is installed in an instance other than the default, (local)\OSI SQL instance. To check the connection strings, do the following:

  1. Navigate to: C:\Program Files\Stanley Security Solutions\Stanley Wi-Q AMS Services\Wi-Q Comm Service\Wi-QCommCore.dll.config file.
  2. Make a backup copy of this file.
  3. Right click on the Wi-QCommCore.dll.config file and open it with notepad.
  4. Locate the section of the config file labeled <!--Database Configuration-->
  5. Locate  database connectionString=”Data Source=(local)\OSI;Initial Catalog=WAMS;Integrated Security=true”
  6. Update the (local)\OSI to the correct SQL name and instance. If you are unsure of this information, please work with local IT person.
  7. If the current user account is not an administrator on the SQL server, please also update the Integrated Security to false and add User ID and Password information.


Applies To

All version of Wi-Q/WAMS 3.0 Software

Additional Information

If you are unfamiliar with XML files or need additional support, please call Software Technical Support. 

Was this article helpful?
0 out of 0 found this helpful
Have more questions? Submit a request

Limited Warranty on Information: The documents contained on this website are distributed as is, without warranty of any kind, either express or implied, including but not limited to implied warranties for the document’s quality, performance, merchantability, or fitness for any particular purpose. Neither Stanley Security Solutions, Inc., nor its dealers or distributors shall be liable to the user or any other person or entity with respect to any liability, loss, nor damage caused or alleged to be caused directly or indirectly by this information.